8
VarioStar 2500
CSA/3100 CSA
mains connec-
tion
NOTE! Inadequately dimensioned electrical installations can lead to serious
damage. The mains lead and its fuse protection must be dimensioned in
accordance with the technical data.
Power source Mains voltage Cable cross-section
VarioStar 2500 CSA 1 x 208 V AWG 12
1 x 230 V AWG 12
1 x 400 V AWG 14
1 x 440/460 V AWG 16
VarioStar 3100 CSA 3 x 230 V AWG 12
3 x 400 V AWG 14
3 x 440/460 V AWG 14
AWG ... American Wire Gauge
The VST 2500 CSA can be operated at a mains voltage of 1x208, 1x230V, 1x400 V or
1x440/460V. These power sources are set to 230V~ in the factory. The tolerance range
in each case is +/- 10%
The VST 3100 CSA can be operated at a mains voltage of 3x230, 3x400 V or 3x440/
460V. These power sources are set to 460V~ in the factory. The tolerance range in
each case is +/- 10%
Important! As an option, the power source can be designed for a special voltage. The
mains voltage is given on the rating plate.