INVERTER SIO Driver
GP-Pro EX Device/PLC Connection Manual
16
External Device Settings
To configure communication settings, use the FUNC/DATA, Up, Down, or PRG/RESET key on the touch panel
located on the front of the External Device. Refer to your External Device manual for details.
1 Turn ON the power of the External Device.
2 Press the PRG/RESET key to move to the program mode.
3 Press the Up or Down key to display the function code group [1.Y_ _ ].
4 Press the FUNC/DATA key.
5 Press the Up or Down key to display the function code you want to set.
6 Press the FUNC/DATA key.
7 Press the Up or Down key to display the setting value.
8 Press the FUNC/DATA key.
9 Press the PRG/RESET key to move to the operation mode.
10 Reboot the External Device.
This completes the External Device settings.
Function Code Setting Setup Description
Y01 1 Station address
Y04 2 Speed
Y05 0 Data length selection
Y06 0 Parity bit selection
Y07 0 Stop bit selection
Y10 2 Protocol selection