INVERTER SIO Driver
GP-Pro EX Device/PLC Connection Manual
47
• The following cables are recommended as the connecting cable for use with RJ-45 connectors.
When using an off-the-shelf LAN cable, use a 10BASE-T/100BASE-TX straight type cable (less than 20m)
compliant to US ANSI TIA/EIA-568A Category 5.
The recommended LAN cables are KB-10T5-01K (1m) and KB-STP-01K (1m) (Shielded LAN cable
compliant with EMC Directive) by SANWA Supply Co., Ltd.
• The recommended connection cable between the terminal block of the Display side and the RJ-45 connector
is the
Furukawa Electric
'
s AWM2789 long-distance cable
.
• Set the termination resistance switch on the External Device as follows:
• RJ-45 connector pin numbers differ depending on the External Device series.
The following pin numbers correspond to each series. Refer to your External Device manual for details.
*3 All GP3000 models except the GP-3200 Series and AGP-3302B
*4 Only a COM port which can communicate by RS-422/485 (2-wire) can be used. (Except PE-4000B, PS5000)
) IPC COM Port (page 5)
*5 Except GP-4203T
*6 All GP4000 models except GP-4100 Series, GP-4*01TM, GP-Rear Module, GP-4201T and GP-4*03T
*7 Except SP-5B00
*8 When using a Terminal Block Conversion Adapter (CA3-ADPTRM-01) instead of the RS-422 Terminal Block
Conversion Adapter, refer to Cable Diagram 2A.
*9 Only a COM port which can communicate by RS-422/485 (2-wire) can be used.
) IPC COM Port (page 5)
Part name Model Remarks
Extension cable by Fuji Electric
Systems Co., Ltd.
CB-5S, CB-3S,
CB-1S
3 cables available in length of 5m,
3m, and 1m.
Series Switch Setting
FVR-E11S SW2 ON
FRENIC-MEGA SW3 ON
FRENIC-Mini
OPC-C1-RS card
SW1 ON
FRENIC-Eco SW3 ON
FRENIC-Multi SW3 ON
Pin No.
FRENIC-MEGA
FRENIC-Mini
FRENIC-Eco
FRENIC-Multi
FVR-E11S
1 VCC (+5V) SEL_TP
2 GND GND
3 NC DX (-)
4 DX (-) DX (+)
5 DX (+) SEL_ANY
6 NC GND
7 GND VCC
8VCC (+5V) VCC