6. To comply with CSA for 200 VAC input models, transient surge suppression shall be installed on
the line side of this equipment and shall be rated 240 V (phase to ground), 240 V (phase to phase),
voltage peak of 4 kV. (3.7 kW (5 HP) or below)
To comply with CSA for 400 VAC input models, transient surge suppression shall be installed on
the line side of this equipment and shall be rated 278 V (phase to ground), 480 V (phase to phase),
suitable for overvoltage category 3, and shall provide protection for a rated impulse withstand
voltage peak of 4 kV.
7. All models rated 380-480 V input voltage ratings shall be connected to TN-C system power source,
i.e. 3-phase, 4-wire, wye (480Y/277V), so that the phase-to-ground rated system voltage is limited
to 300 V maximum.
8. Maximum surrounding air temperature rating of 50 ºC (122 °F)..
9. For use in pollution degree 2 environments only.