1-2. Outdoor unit
Type Inverter heat pump
Model name AOHG09KVCBN AOHG12KVCBN AOHG14KVCBN
Power supply 230 V ~ 50 Hz
Available voltage range 198—264 V
Starting current A 3.6 4.9 6.2
Fan
Airflow rate
Cooling
m
3
/h
1,550 1,830 2,210
Heating 1,690 2,100 2,100
Type × Q'ty Propeller × 1
Motor output W 49
Sound pressure level *1
Cooling
dB (A)
40 44 51
Heating 46 52 50
Sound power level
Cooling
dB (A)
54 58 63
Heating 58 62 63
Heat exchanger type
Dimensions
(H × W × D)
mm
Main1: 588 × 881 × 18.19
Main2: 588 × 851 × 18.19
Fin pitch 1.3
Rows × Stages 2 × 28
Pipe type Copper
Fin type
Type (Material) Aluminium
Surface treatment PC Fin
Compressor
Type × Q'ty DC TWIN ROTARY
Motor output W 810 925
Refrigerant
Type (Global warming potential) R32 (675)
Charge g 940
Refrigerant oil
Type FW68S RmM68AF
Amount
cm
3
350 400
Enclosure
Material Steel sheet
Color
BEIGE
Dimensions
(H × W × D)
Net
mm
632 × 799 × 290
Gross 692 × 940 × 375
Weight
Net
kg
36 38
Gross 40 42
Connection pipe
Size
Liquid
mm (in)
Ø 6.35 (Ø 1/4)
Gas Ø 9.52 (Ø 3/8)
Method Flare
Pre-charge length
m
15
Max.length 20
Max. height difference 15
Operation range
Cooling
°C
-10 to 46
Heating -25 to 24
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 5 m, Height difference: 0 m.
• Protective function might work when using it outside the operation range.
• *1: Sound pressure level
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.