1-2. Heating operation
A sensor (room temperature thermistor) built in indoor unit body will usually perceive difference or
variation between setting temperature and present room temperature, and controls operation fre-
quency of compressor.
If the room temperature is 6.0 °C lower than a set temperature, the compressor operation frequen-
cy will attain to maximum performance.
If the room temperature is 1.0 °C higher than a set temperature, the compressor will be stopped.
When the room temperature is within the range of +1.0°C to -6.0°C of the setting temperature, the
compressor frequency is controlled within the range shown below.
Compressor frequency range
Model name Minimum frequency Maximum frequency
AGHG09KVCB 8 120
AGHG12KVCB
AGHG14KVCB
10 130
Limit of maximum speed based on outdoor temperature
In heating operation, maximum frequency is defined by outdoor temperature and fan mode.
A zone
12°C
B zone
14°C
C zone
-10°C
-12°C
Outdoor
temperature rises
Outdoor
temperature drops
Unit: rps
Model name
Outdoor
temperature
zone
Indoor unit fan mode
HIGH MED LOW QUIET
AGHG09KVCB
A zone 120 74 68 68
B zone 120 74 63 39
C zone 120 74 63 26
AGHG12KVCB
AGHG14KVCB
A zone 130 130 74 74
B zone 130 94 68 42
C zone 130 94 68 28
1-2. Heating operation - (04-3) - 1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AGHG12KVCB and is the answer not in the manual?

Fujitsu AGHG12KVCB Specifications

General IconGeneral
BrandFujitsu
ModelAGHG12KVCB
CategoryAir Conditioner
LanguageEnglish

Related product manuals