SPLIT TYPE
ROOM AIR CONDITIONER
Models Indoor unit Outdoor unit
AOU36RLXFZH
AOU45RLXFZ
INVERTER MULTI
SERVICE
INSTRUCTION
R410A
Compact Wall Mounted
Wall Mounted / Floor
Compact Cassette / Slim Duct
ARU7RLF
ARU9RLF
ARU12RLF
ARU18RLF
ARU24RLF
AUU7RLF
AUU9RLF
AUU12RLF
AUU18RLF
ASU18RLF
ASU7RLF1
ASU9RLF1
ASU12RLF1
AGU9RLF
AGU12RLF
AGU15RLF
ASU24RLF

Table of Contents

Other manuals for Fujitsu AGU12RLF

Questions and Answers

  • M
    Mark OrtizAug 13, 2025
    What to do if my Fujitsu Air Conditioner remote is not working due to a communication error?
    • S
      Steve FieldsAug 14, 2025
      If you're experiencing a Wired Remote Controller Communication Error with your Fujitsu Air Conditioner, check the voltage. If it's DC12V, the remote control has failed and should be replaced. If it's DC 0V, the Controller PCB has failed and should be replaced after rechecking the remote control.
  • W
    wdeckerAug 16, 2025
    What to do if my Fujitsu Air Conditioner has a drainage error?
    • D
      Dylan PerezAug 17, 2025
      If your Fujitsu Air Conditioner is experiencing drainage issues, start by inspecting the float switch for proper operation using a meter to check its on/off switching. If the float switch is defective, replace it. Also, examine the drain hose for any clogs and clear them if necessary. If these steps don't resolve the issue, consider replacing the controller PCB.
  • H
    Heather FloresAug 20, 2025
    How to fix a Fujitsu AGU12RLF Air Conditioner indoor unit fan motor error?
    • W
      whitney77Aug 20, 2025
      If you're encountering an indoor unit fan motor error with your Fujitsu Air Conditioner, check first the fan and bearing. If either is damaged, replace them. If the motor itself is faulty, replace the indoor unit fan motor. If these steps do not resolve the issue, replace the controller PCB.
  • P
    Patrick BrooksAug 25, 2025
    What to do if my Fujitsu AGU12RLF Air Conditioner shows an indoor room thermistor error?
    • A
      Angela MasonAug 26, 2025
      If your Fujitsu Air Conditioner displays an indoor room thermistor error, begin by checking the connector to ensure it is securely attached and properly connected, and verify that the thermistor cable is not open. If the thermistor is either open or shorted, replace it and then reset the power.
  • Y
    yreedAug 28, 2025
    How to troubleshoot an Indoor Unit Model Information Error on my Fujitsu Air Conditioner?
    • R
      Regina VillarrealAug 28, 2025
      If your Fujitsu Air Conditioner is showing an Indoor Unit Model Information Error, check for external causes such as noise and ensure the ground connection is properly connected. Also, inspect all connectors for looseness or incorrect wiring, and check the PCB for any shorts or corrosion. If the problem persists, consider replacing the Controller PCB.
  • T
    tammy25Sep 1, 2025
    What does an Indoor Unit Capacity Error mean on my Fujitsu AGU12RLF?
    • A
      Alexandra HermanSep 1, 2025
      If your Fujitsu Air Conditioner is showing an Indoor Unit Capacity Error, first verify the total capacity of the connected indoor units. If an abnormal condition is found, correct it by referring to the Installation Manual or Design & Technical Manual. If the problem persists, replace the Main PCB of the Outdoor unit.
  • D
    Dominique RiceSep 5, 2025
    How to fix a Serial Communication Error (Serial Reverse Transfer Error) on a Fujitsu Air Conditioner?
    • S
      Shane ReyesSep 5, 2025
      If your Fujitsu Air Conditioner displays a Serial Communication Error (Serial Reverse Transfer Error), check all connection lines between the indoor and outdoor units for any looseness or disconnections, referring to the Installation Manual or Data & Technical Manual for correction. Also, check the voltage of the power supply, ensuring it appears at the outdoor unit terminal L1 - L2 within the range of AC187V - 253V. Check that the indicated value swings between AC90V and AC270V at outdoor unit terminal 1 - 3. If the outdoor fan motor, active filter module, or IPM is abnormal, replace the corresponding part. If all parts are normal, replace the Main PCB.
  • M
    Mary FrancoSep 9, 2025
    How to resolve a Damper (Open/Close) simultaneous detection Limit switch error on a Fujitsu AGU12RLF Air Conditioner?
    • M
      Michael SinghSep 9, 2025
      If your Fujitsu Air Conditioner displays a Damper(Open/Close) simultaneous detection Limit switch error, replace the limit switch if it is defective. If the problem persists, replace the Controller PCB.

Summary

DESCRIPTION OF EACH CONTROL OPERATION

CAPACITY CONTROL

Explains compressor frequency determination based on temperature and unit settings.

AUTO CHANGEOVER OPERATION

Details automatic switching between Heating, Cooling, Dry, and Monitoring modes based on temperature.

INDOOR FAN CONTROL

Covers indoor fan speed settings, airflow modes, and adjustments for various operations.

LOUVER CONTROL

Explains vertical and horizontal louver adjustments, swing operations, and their settings.

OUTDOOR FAN CONTROL

Shows fan speeds for outdoor units in Cooling and Heating modes.

COMPRESSOR CONTROL

Details compressor operation frequency ranges and control strategies during start-up.

TIMER OPERATION CONTROL

Explains wireless remote controller timer settings: ON/OFF, Program, and Sleep timers.

ELECTRONIC EXPANSION VALVE CONTROL

Describes pulse ranges for electronic expansion valve control based on operation mode and temperature.

TEST OPERATION CONTROL

Outlines procedures for test run operations using wireless and wired remote controllers.

PREVENT TO RESTART FOR 3 MINUTES (3 MINUTES ST)

Explains the 3-minute delay mechanism before the compressor restarts after a stop.

4-WAY VALVE EXTENSION SELECT

Details the 3-minute delay for 4-way valve switching when changing from Cooling to Heating mode.

AUTO RESTART

Describes how operation contents are memorized and resumed automatically after a power interruption.

MANUAL AUTO OPERATION

Explains manual auto operation mode for use without a remote control or in emergencies.

COMPRESSOR PREHEATING

Details the process of heating the compressor to prevent damage in low ambient temperatures.

POWERFUL OPERATION (For ASU*RLF1; AGU*RLF type)

Explains the powerful operation mode for maximum indoor/outdoor unit output.

MINIMUM HEAT OPERATION

Describes the minimum heat operation performance when activating the MIN. HEAT button.

ECONOMY OPERATION

Explains the economy operation for reduced output, saving energy in cooling and heating.

HEAT INSULATION CONDITION (BUILDING INSULATION)

Setting to improve room temperature control suitability for buildings with high insulation.

THERMO CONTROL (FOR INDOOR UNIT SENSOR)

Details thermo control operation and compressor cycles based on the indoor unit sensor.

THERMO CONTROL (FOR WIRED REMOTE SENSOR)

Details thermo control operation and compressor cycles based on the wired remote sensor.

BASE HEATER OPERATION (For AOU36 RLXFZH)

Describes the base heater operation conditions and controls, primarily for heating.

FRESH AIR CONTROL (For AU type)

Explains the synchronization of the fresh air fan with indoor fan operation for air circulation.

EXTERNAL ELECTRICAL HEATER CONTROL (For AR type)

Details the conditions and operation of the external electrical heater.

DRAIN PUMP OPERATION (For AU; AR type)

Explains drain pump operation cycles during Cooling/Dry and Heating/Fan modes.

AIR OUTLET SELECTION (DAMPER CONTROL )( For AG type)

Details how to set air outlets for upper/lower airflow or upper airflow only.

DEFROST OPERATION CONTROL

Explains conditions for starting, integrating, and completing defrost operation based on temperatures.

CHECK RUN OPERATION (AUTOMATIC WIRING CORRECTION)

Procedure for check run and automatic wiring correction to verify and correct unit connections.

VARIOUS PROTECTIONS

Details protections like Discharge Gas Temperature Over Rise, Current Release, and Cooling Pressure Over Rise.

PUMP DOWN OPERATION

Procedure for pump down operation when moving or discarding the air conditioner unit.

TEST RUN (For Outdoor unit)

Method for performing test runs on the outdoor unit to check its operation and components.

TROUBLE SHOOTING

ERROR DISPLAY

Lists error contents, indoor unit display patterns, and corresponding troubleshooting steps.

TROUBLE SHOOTING WITH ERROR CODE

Provides detailed troubleshooting steps for specific error codes, starting with Serial Communication Error.

TROUBLE SHOOTING WITH NO ERROR CODE

Guides on diagnosing issues like "No Power" without specific error codes.

SERVICE PARTS INFORMATION

Lists service parts and their diagnostic procedures, including Compressor, Fan Motor, and PCBs.

Fujitsu AGU12RLF Specifications

General IconGeneral
Power Supply220-240V, 50Hz
RefrigerantR410A
Indoor Unit Dimensions (WxHxD)790 x 275 x 202 mm
Outdoor Unit Dimensions (WxHxD)660 x 530 x 240 mm
Indoor Unit Weight9 kg
Energy Efficiency Ratio (EER)11 BTU/W
Indoor Unit Noise Level21 dB
Cooling Capacity12000 BTU/h

Related product manuals