3-2. Outdoor fan control
¢ Outdoor fan motor
This outdoor unit has a DC fan motor. (Control method is different between AC and DC motors.)
¢ Fan speed
Model: AOYG09KVCA
Fan speed is defined by outdoor temperature and compressor frequency.
• Outside air temperature zone selection
21°C
Outside air
temperature rises
Z zone
Y zone
F zone
G zone
Outside air
temperature drops
12°C
2°C
19°C
10°C
0°C
Unit: rpm
Fan step
Cooling
Heating
Dry Cooling or dry at low outdoor temp.
Y zone Y zone Z zone F zone G zone
S-HIGH2 — 1,120 — — — —
S-HIGH1 990 1,120 — — — —
HIGH 990 870 — — — —
10 — 870 — — — —
9 990 870 990 990 270 250
8 920 870 920 630 270 250
7 920 800 920 630 270 230
6 810 800 810 630 250 220
5 810 710 810 610 250 220
4 810 710 810 450 250 220
3 570 500 570 310 220 220
2 570 500 570 200 210 200
1 520 500 520 200 200 200
NOTE:
After defrost control on the heating mode, the fan speed is kept higher regardless of the
compressor frequency.
Fan speed after defrost control: 1,120 rpm
3-2. Outdoor fan control
- (04-14) - 3. Fan control
CONTROL AND
FUNCTIONS