En-17
11
Cooling capacity
shift (*1)
Normal mode
11
00
z
Save energy mode 0 1
High power mode 1 0 2
High power mode 2 0 3
Prohibited 0 4
Set this item when necessary.
12
Heating capacity
shift (*1)
Normal mode
12
00
z
Save energy mode 0 1
High power mode 1 0 2
High power mode 2 0 3
Set this item when necessary.
13 Prohibited (Factory default) 1300
z
14 Prohibited (Factory default) 1400
z
15 Prohibited (Factory default) 1500
z
17
Height difference
between indoor
units (*1)
Standard
17
00
z
Forbidden 0 1
Height difference 0 2
Prohibited 0 3
Prohibited 0 4
If installing the indoor units (even only one set) to a lower floor than the outdoor
unit, and the height difference between the indoor units is 3 m or greater (i.e., if
installing the indoor units on separate floors), set “02 (height difference)”.
20
Switching be-
tween batch stop
or emergency
stop (*1)
Batch stop
20
00
z
Emergency stop 0 1
This mode selects the pattern of the stop function to be operated by the external
input terminal (CN134).
• Batch stop: The stop of all indoor units connected to same refrigerant system
due to input signal coming from CN134.
• Emergency stop: When emergency stop is actuated, the indoor unit does not
accept the operation command from the remote controller. On the other hand,
when the emergency stop is released (no input from CN134), the air conditioner
does not return to the original operation until the indoor unit is turned on by the
remote controller.
21
Operation mode
selecting method
(*1)
Priority given to the first
command
21
00
z
Priority given to external
input of outdoor unit
01
Priority given to administra-
tive indoor unit
02
Select the priority setting of the operation mode.
• Priority given to the first command: Priority is given to the operation mode which
is set first.
• Priority given to external input of outdoor unit: Priority is given to the operation
mode which is set by the external input terminal (CN132).
• Priority given to administrative indoor unit: Priority is given to the operation
mode of the administrative indoor unit which is set by the wired remote control-
ler.
22
Snow falling
protection fan
mode (*1)
Enable
22
00
z
Disable 0 1
This mode operates the fans of outdoor units in order to prevent the units from stop-
ping operation when they are covered by snow.
23
Interval setting
for snow falling
protection fan
mode (*1)
Standard (30 minutes)
23
00
z
Short 1 (5 minutes) 0 1
Short 2 (10 minutes) 0 2
Short 3 (20 minutes) 0 3
When the snow falling protection fan mode is set, the operation interval of the fans of
outdoor units can be selected.
24
High static pres-
sure mode
Standard
24
00
z
High static pressure 1
(equivalent to 30 Pa)
01
High static pressure 2
(equivalent to 80 Pa)
02
Prohibited 0 3
When installing a duct to the blow-off outlet of an outdoor unit, set the high static
pressure mode according to the static pressure of the duct to be installed.
Furthermore, use this setting if the air blow of an outdoor unit is poor, such as when
installed in a place with a low ceiling.
25 Prohibited (Factory default) 2500
z
26 Prohibited (Factory default) 2600
z
27 Prohibited (Factory default) 2700
z
28 Prohibited (Factory default) 2800
z
29 Prohibited (Factory default) 2900
z
30
Energy saving
level setting (*1)
Level 1 (stop)
30
00
z
Level 2
(operated at 40% capacity)
01
Level 3
(operated at 60% capacity)
02
Level 4
(operated at 80% capacity)
03
Level 5
(operated at 100% capacity)
04
The capacity limit can be selected by the external input terminal (CN133) when
operating with the “Energy Saving Peak Cut function”.
The lower the level, the more the effect of energy saving, but the cooling/heating
performance will also drop.
32 Prohibited (Factory default) 3 2 0 0
z
33 Prohibited (Factory default) 3 3 0 0
z
40
Capacity priority
setting (in low
noise mode) (*1)
Off (quiet priority)
40
00
z
On (capacity priority) 0 1
If the cooling/heating performance becomes insufficient when the low noise mode
is set, it is possible to set “capacity priority” that automatically cancels the low
noise mode (once performance is restored, the mode will automatically return to
the low noise mode).
41
Low noise mode
setting (*1)
Off (Normal)
41
00
z
On (Low noise mode) 0 1
42
Low noise mode
operation level
setting
Level 1
42
00
z
Level 2 0 1
Level 1: The operating sound lowers from about 3 to 5 dB(A) more than the rated
value
Level 2: The operating sound lowers from about 3 to 5 dB(A) more than the Level
1
53
Intelligent refrig-
erant control
Enable
53
00
z
Disable 0 1
Enable only evaporation
temperature control
02
Enable only condensation
temperature control
03
61 Prohibited (Factory default) 6 1 0 0
z
62 Prohibited (Factory default) 6 2 0 0
z
63 Prohibited (Factory default) 6 3 0 0
z
70
Electricity meter
No. setting 1 (*2)
Setting number (x00)
70
00
z
Setting number (x01) 0 1
······ ··· ···
Setting number (x98) 9 8
Setting number (x99) 9 9
Set the ones digit and tens digit of the No. of the electricity meter connected to
CN135.
71
Electricity meter
No. setting 2 (*2)
Setting number (0xx)
71
00
z
Setting number (1xx) 0 1
Setting number (2xx) 0 2
Set the hundreds digit of the No. of the electricity meter connected to CN135.
72
Electricity meter
pulse setting 1
(*3)
Setting number (xx00)
72
00
z
Setting number (xx01) 0 1
⁞⁞
Setting number (xx98) 9 8
Setting number (xx99) 9 9
Set the ones digit and tens digit of the No. of the electricity meter pulse setting
connected to CN135.
73
Electricity meter
pulse setting 2
(*3)
Setting number (00xx)
73
00
z
Setting number (01xx) 0 1
······ ··· ···
Setting number (98xx) 9 8
Setting number (99xx) 9 9
Set the hundreds digit and thousands digit of the electricity meter pulse setting
connected to CN135.
*1: Do not set this for outdoor units with subordinate setting.
*2: When electricity meter No. is set to “000” and “201 to 299”, the pulses input to
CN135 become ineffective. Available setting number is "001" to "200"
*3: When the electricity meter pulse setting is set to “0000”, the pulses input to CN135
become ineffective. Available setting number is "0001" to "9999"
(1) Turn on the power of the outdoor unit and enter standby mode.
When system is normal
POWER/MODE lamp lights up. (ERROR
lamp is off.)
POWER/MODE
lamp: ON
ERROR lamp: OFF
SELECT button
ENTER
button
MODE/EXIT
button
7 segment LED
indicator: OFF
When system is abnormal
Check the settings as there is an error in
the settings for outdoor unit address (DIP
switch SET3-1, 2) or number of connected
subordinate units (DIP switch SET3-3, 4).
POWER/MODE
lamp: ON
7 segment LED
indicator: "-"
display
ERROR lamp: Blinking
9378945708-02_IM_L9.indb 179378945708-02_IM_L9.indb 17 2022/1/20 15:34:382022/1/20 15:34:38