3.3.1 When install nearby limited height wall
(1) Single and multiple installations
• There are no restrictions on the height of the side wall.
Provide installation spaces L1 and L2 in accordance with the table below according to the
wall height (front side, rear side) conditions.
• Provide installation spaces other
than L1 and L2 in accordance with
the conditions shown in the figure
below.
• Ventilation resistance can be
ignorable when the distance from
a wall or product, etc. is larger
than 2 m.
Wall height condi-
tion [mm]
Necessary
installation
space [mm]
When H1 is 1,500 or less L1 500
When H1 is 1,500 or more L1 500 + h1 ÷ 2
When H2 is 500 or less L2 100
When H2 is 500 or more L2 100 + h2 ÷ 2
Single installation
500
1,500
L1
L2
H1
h1
H2
h2
Unit: mm
10 or
more
30 or
more
Multiple installations
500
1,500
L1
L2
H1
h1
H2
h2
Unit: mm
30 or
more
20 or
more
20 or
more
20 or
more
(2) Concentrated installation
• Provide installation spaces L3,
L4, and L5 in accordance with
the table below according to
the wall height (front side, rear
side) conditions.
• Provide installation spaces
other than L3, L4, and L5 in
accordance with the conditions
shown in the figure below.
• Ventilation resistance can be
ignorable when the distance
from a wall or product, etc. is
larger than 2 m.
Wall height condition
[mm]
Necessary in-
stallation space
[mm]
When H3 is 1500 or less L3 500
When H3 is 1500 or more L3 500 + h3 ÷ 2
When H4 is 500 or less L4 200
When H4 is 500 or more L4 200 + h4 ÷ 2
When H5 is 500 or less L5 200
When H5 is 500 or more L5 200 + h5 ÷ 2
500
1,500
L3
L2
H3
h3
H4
h4
L5
L5
500
H5
h5
500
H5
h5
Unit: mm
20 or
more
20 or
more
800 or
more
800 or
more
1,500
1,500
1,500
L5
L5
500
1,500
L3
L2
H3
h3
H4
h4
500
H5
h5
500
H5
h5
Unit: mm
20 or
more
1,500
20 or
more
1,000
or more
500 or
more
3.3.2 When install near unlimited height wall
(1) Single and multiple installations
• There are no restrictions on the height of the wall.
• The wall (without height restrictions) must not exist on the both sides (left / right) of
outdoor unit. Also, must not exist on the both sides (front / rear) of outdoor unit.
• Provide installation spaces other than L6 in accordance with the conditions shown in the
figure below.
• Ventilation resistance can be ignorable when the distance from a wall or product, etc. is
larger than 2 m.
When installing with the
rear of the outdoor unit
facing the wall side
Condition
Necessary installa-
tion space
When B 400 (mm) L6 200 (mm)
When 20 B < 400 (mm)
L6 200 + (400 - B) × 3
(mm)
Single installation
Unit: mm
200 or
more
100 or
more
Multiple installations
B
B
L6
Unit: mm
200 or
more
Example :
When B is made 200 mm
L6 200 + (400-200) × 3 = 800 mm
Unit: mm
200 or
more
200
200
800 or
more
9378945708-02_IM_L9.indb 49378945708-02_IM_L9.indb 4 2022/1/20 15:34:372022/1/20 15:34:37