04-04
3. COMPRESSOR FREQUENCY LIMITED BY OUTDOOR TEMPERATURE
Frequency of compressor is limited
by outdoor temperature as shown below.
Minimum frequency in cooling or dry operation
AOU24RGLX
under 14 ˚F
(-10 ˚C)
40 rps
over 14 ˚F (-10 ˚C)
under 32 ˚F (0 ˚C)
over 32 ˚F (0 ˚C)
under 50 ˚F (10 ˚C)
over 50 ˚F (10 ˚C)
under 100 ˚F (38 ˚C)
over 100 ˚F
(38 ˚C)
25 rps 25 rps12 rps32 rps
AOU30RGLX 25 rps16 rps40 rps 25 rps32 rps
AOUG36LMAS1
under 26.6 ˚F
(-3 ˚C)
26 rps
over 26.6 ˚F (-3 ˚C)
under 120.2 ˚ F (49 ˚C)
over 120.2 ˚F
(49 ˚C)
25 rps20 rps
AOUG48LMAS1