SERVICE PARTS INFORMATION 5
Check Point : AU*24LUAR
Red - Violet
Red - Violet
Red - Black
White - Red
Read Wire
120 8%
55.3 8%
61.2 8%
283 8%
Resistance value
(AC)
Thermal protector
Pr
BLUE
VIOLET
RED
BLACK
WHITE
150°C
Check Point : AU*30/ 36/ 45/ 54LUAS
44.5 10%
40.5 10%
Resistance value
(AC)
Thermal protector
130°C
Pr
1
1 3
2
3
The connector
inserting numbers
2 3
at 20°C
at 20°C
Indoor Unit Fan Motor
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
07-33