Outdoor fan : OFF
Compressor speed : 0 rps
EEV : 480pulse
4-way valve : OFF
Compressor speed : 90rps
3. Defrost Flow Chart
The defrosting shall proceed by the integrating operation time, outdoor temperature
and outdoor heat exchanger temperature as follows.
(Not defrosted for 10 minutes)
Heating operation start : Compressor ON
Outdoor HEX temp.: Over 16°C
or
Compressor ON time: Maximum 15 minutes
Defrost end
Tn < - 17°C
Tn <
Outside temp.- 7°C
or
Tn < - 20°C
Integrating defrost
Defrost Indicator:
[Operation lamp]
7 sec ON / 2 sec OFF
Defrost start
Normal defrost
Outside temp. > -10°C
-20°C< Outside temp.< -10°C
Tn <
Outside temp.- 7°C
or
Tn < - 30°C
Outside temp.< -20°C
=
=
Compressor
OFF count :
40 times
(Less than 10min.)
Compressor
integrating
operation:
Over 240 min.
Outdoor
heat exchanger
temperature:
Below - 3°C
Compressor
integrating
operation:
Over 213 min.
Outdoor
heat exchanger
temperature:
Below - 5°C
Intermittent operation Continuous operation
=
= =
=
=
Tn -Tn10<-5deg
Tn -Tnb <-2deg
However,Tn< 6°C
=

Other manuals for Fujitsu AOU12RLS2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOU12RLS2 and is the answer not in the manual?

Fujitsu AOU12RLS2 Specifications

General IconGeneral
BrandFujitsu
ModelAOU12RLS2
CategoryAir Conditioner
LanguageEnglish

Related product manuals