Indoor heat exchanger
temperature rises
Indoor heat exchanger
temperature drops
The maximum value of the indoor fan speed is set as shown in Fig. 6, based on the detected
temperature by the indoor heat exchanger sensor on heating mode.
(Fig.6 : Cool air prevention control)
01-06
6. COOL AIR PREVENTION CONTROL (Heating mode)
47°C
40°C
37°C
Cool air prevention
30°C
S-Lo
40°C
28°C
32°C
35°C
<Before 7 minutes upon running the compressor>
Lower of "Hi" and "setting fan speed"
Lower of "Me+" and "setting fan speed"
Lower of "Lo" and "setting fan speed"
Indoor heat exchanger
temperature rises
Indoor heat exchanger
temperature drops
47°C
40°C
40°C
35°C
<After 7 minutes upon running the compressor>
Lower of "Hi" and "setting fan speed"
Lower of "Me+" and "setting fan speed"
Lower of "Lo" and "setting fan speed"
Switch the airflow [Auto] at cooling mode, and the indoor fan motor will run as shown in Fig.7.
7. MOISTURE RETURN PREVENTION CONTROL (Cooling mode& Dry mode)
( Fig.7 : Indoor fan control )
Compressor
ON
OFF
Indoor fan
Setting air flow
Indoor fan
(as shown in Table 6)
S-Lo
OFF
10 30 60 180 60 180 60 10 30
(sec)
( Table 6 : Indoor fan speed )
X zone J zone
AS* G09/ 12LECB
680rpm 600rpm
Y zone
0 480rpm 680rpm
Dry
Cooling