9. Electrical characteristics
Model name AOU9RLFC AOU12RLFC AOU18RLFC
Power
supply
Voltage V 208/230~
Frequency Hz 60
MCA *
1
A 13.4 17.3
Starting current A 4.1 6.7 7.7
Wiring
spec. *
2
MAX. CKT. BKR *
3
A 15 20
Power cable AWG 14 12
Connection
cable *
4
Size AWG 14
Limited wiring
length
ft (m) 60 (18) 75 (22)
*1: Minimum Circuit Ampacity (Calculation based on UL1995)
*2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate de-
vices complied to the regional standard.
*3: Maximum Circuit Breaker
*4: Limit voltage drop to less than 2%. If voltage drop is 2% or more, increase cable conductor size.