EasyManua.ls Logo

Fujitsu AOU48RLXFZ1 - Refrigerant Recovery Method

Fujitsu AOU48RLXFZ1
38 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
En-25
Refrigerant recovery method7. 4.
Please perform the refrigerant recovery
according to the local law and rules.
The refrigerant recovery of this type
of equipment must be performed by a
refrigerant recovery machine.
Turn on both the power supplies of the
outdoor unit and the branch boxes.
Press the “MODE/EXIT” button of the
outdoor unit when all units are in stop
operation state.
Match the 7 seg. display to “F3” by
pushing the SELECT button.
Press the “ENTER” button.
Match the 7 seg. display to “21” by
pushing the “SELECT” button.
Press the “ENTER” button for about 5
seconds.
Turn off the power supplies of all units
when “P.oFF” is displayed.
Perform the refrigerant recovery with
the refrigerant recovery machine.
It can not be operated in the “P.oFF” state.
Please turn on the power supplies of all units again in case of performing operation.
MODE/EXIT
MODE/EXIT
SELECT
×2
×2
SELECT
ENTER
ENTER
(Blinking) (Blinking)
(Blinking)
(Blinking)
: Press the “MODE/EXIT” button.
: Press the “SELECT” button.
: Press the “ENTER” button.
7 seg.display
SELECT
ENTER
9379069342-02_IM.indb 25 17/5/2556 11:49:59