Low noise mode (CN931)10. 2. 2.
•Thisfeaturesreducestheoperatingsoundof
the outdoor unit from the normal sound. The
air conditioner is set to the “Low noise mode”
when closing the contact input of a commercial
timer or ON/OFF switch to a connector on the
outdoor control PC board.
* Performance may drop depending on the
outside air temperature condition, etc.
Input Signal
Low noise mode
ON
ON
OFF
OFF
* Set the “Low noise mode” level, refer to
“8.2.Function settings”.
Input Signal ···ON : Low noise mode
···OFF : Normal operation
External input priority mode (CN932)10. 2. 3.
•Itispossibletoswitchtocoolingoperationand
heating operation by using external input.
Input Signal
Priority mode
ON
Heating
OFF
Cooling
* Set the “External input priority mode” , refer to
“8.2.Function settings”.
Input Signal ···ON : Heating operation
···OFF : Cooling operation
Peak cut mode (CN933)10. 2. 4.
•Operationthatsuppressedthecurrentvalue
can be performed by means of the connected
unit. The air conditioner is set to the Peak
cut mode by applying the contact input of a
commercial ON/OFF switch to a connector on
the outdoor control PC board.
Input Signal
Peak cut mode
ON
ON
OFF
OFF
* Set the “Peak cut mode” level , refer to
“8.2.Function settings”.
Input Signal ···ON : Peak cut mode
···OFF : Normal operation
Stop operation mode (CN934)10. 2. 5.
•ItispossibletoswitchtoBatchstopor
Emergency stop and Normal operation by using
external input.