En-9
Single outdoor unit installation3. 3. 1.
When the upward area is open (Unit:mm(in.))
(1) Obstacles at rear only (2) Obstacles at rear and
sides only
(3) Obstacles at front only (4) Obstacles at front and
rear only
1000(39-3/8) or more
200(7-7/8)
300(11-13/16)
200(7-7/8)
1000(39-3/8) more
150(5-29/32)
150(5-29/32)
When an obstruction is present also in the upward area (Unit : mm(in.))
(1) Obstacles at rear and above only
(2) Obstacles at rear, sides, and above only
300(11-13/16)
Max. 500(19-11/16)
1000(39-3/8)
1500(59-1/16)
250(9-27/32)
250(9-27/32)
500 (19-11/16)
Max. 500 (19-11/16)
Multiple outdoor unit installation3. 3. 2.
Provide at least 25mm (1in.) of space between the outdoor units if multiple units are installed.
When routing the piping from the side of an outdoor unit, provide space for the piping.
No more than 3 units must be installed side by side.
When 3 units or more are arranged in a line, provide the space as shown in the following example when an
obstruction is present also in the upward area.
When the upward area is open (Unit: mm(in.))
(1) Obstacles at rear only (2) Obstacles at front only
(3) Obstacles at front and rear only
1500(59-1/16) or more
300(11-13/16)
500(19-11/16)
1500(59-1/16) or more
When an obstruction is present also in the upward area (Unit: mm(in.))
Obstacles at rear and above only
1500(59-1/16)
500(19-11/16)
Max. 300(11-13/16)
1500(59-1/16)
9379069342-02_IM.indb 9 17/5/2556 11:49:30