Heating thermostat on for humidifier
Situation
Indoor unit
Mode
Function
setting
Rotary SW
External output
Heating
thermostat on
no. 60
Heating
thermostat on
Indoor unit fan
operation
status
Example of
individual
connection
5 60-05 7 CN47
Not used
6 60-06 8 Output3
7 60-07 9 Output2
8 60-08 A Output1
Example of individual connection
External output: Heating thermostat on
Humidifier
Operation status
The heating thermostat output for CN47, Output1, Output2, and Output3 will be on when comp on
or external heater on.
The heating thermostat output will be off when comp off and external heater off.
Heating operation
Heating thermostat
On output
External heater
output On / Off
Comp. On / Off
On
On
On
On
On
Off
Off
Off
Off
Off
Fan
Cool air prevention
- 51 -
6-4. Details of function 6. External input and output
DUCT TYPE
AMUG24-48LMAS
DUCT TYPE
AMUG24-48LMAS

Table of Contents

Other manuals for Fujitsu AOUG48LMAS1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOUG48LMAS1 and is the answer not in the manual?

Fujitsu AOUG48LMAS1 Specifications

General IconGeneral
BrandFujitsu
ModelAOUG48LMAS1
CategoryAir Conditioner
LanguageEnglish

Related product manuals