12) Operating temperature switching of external heaters
Sets the temperature conditions when the external heater is ON.
For details, refer to “External heater output” in Chapter 6-4. "Details of function" on page 27.
Function
number
Setting
value
Setting description
Factory
setting
Setting value of function 61:
00 01 to 09
Heater: On Heater: Off Heater: On Heater: Off
62
00 -5.4 °F (-3 °C) -1.8 °F (-1 °C) -0.9 °F (-0.5 °C) 0.9 °F (0.5 °C) ♦
01 -3.6 °F (-2 °C) -1.8 °F (-1 °C) -1.8 °F (-1 °C) 0.9 °F (0.5 °C)
02 -3.6 °F (-2 °C) -1.8 °F (-1 °C) -3.6 °F (-2 °C) 0.9 °F (0.5 °C)
03 -5.4 °F (-3 °C) -1.8 °F (-1 °C) -5.4 °F (-3 °C) 0.9 °F (0.5 °C)
04 -7.2 °F (-4 °C) -1.8 °F (-1 °C) -7.2 °F (-4 °C) 0.9 °F (0.5 °C)
05 -9.0 °F (-5 °C) -1.8 °F (-1 °C) -9.0 °F (-5 °C) 0.9 °F (0.5 °C)
06 -5.4 °F (-3 °C) -0.9 °F (-0.5 °C) -0.9 °F (-0.5 °C) 0 °F (0 °C)
07 -3.6 °F (-2 °C) -0.9 °F (-0.5 °C) -1.8 °F (-1 °C) 0 °F (0 °C)
08 -3.6 °F (-2 °C) -0.9 °F (-0.5 °C) -3.6 °F (-2 °C) 0 °F (0 °C)
09 -5.4 °F (-3 °C) -0.9 °F (-0.5 °C) -5.4 °F (-3 °C) 0 °F (0 °C)
10 -7.2 °F (-4 °C) -0.9 °F (-0.5 °C) -7.2 °F (-4 °C) 0 °F (0 °C)
11 -9.0 °F (-5 °C) -0.9 °F (-0.5 °C) -9.0 °F (-5 °C) 0 °F (0 °C)
12 -5.4 °F (-3 °C) 0 °F (0 °C) -0.9 °F (-0.5 °C) -0.9 °F (-0.5 °C)
13 -3.6 °F (-2 °C) 0 °F (0 °C) -1.8 °F (-1 °C) -0.9 °F (-0.5 °C)
14 -3.6 °F (-2 °C) 0 °F (0 °C) -3.6 °F (-2 °C) -0.9 °F (-0.5 °C)
15 -5.4 °F (-3 °C) 0 °F (0 °C) -5.4 °F (-3 °C) -0.9 °F (-0.5 °C)
16 -7.2 °F (-4 °C) 0 °F (0 °C) -7.2 °F (-4 °C) -0.9 °F (-0.5 °C)
17 -9.0 °F (-5 °C) 0 °F (0 °C) -9.0 °F (-5 °C) -0.9 °F (-0.5 °C)
13) Outdoor temperature zone boundary temperature A
Setting required if changing of the outdoor temperature setting for heat pump prohibition zone is re-
quired when auxiliary heater control by outdoor temperature 1 and 2 are performed on the indoor
unit. For details, refer to “External heater output” in Chapter 6-4. "Details of function" on page 27.
Function number Setting value Setting description Factory setting
66
00 -4.0 °F (-20 °C) ♦
01 -0.4 °F (-18 °C)
02 3.2 °F (-16 °C)
03 6.8 °F (-14 °C)
04 10.4 °F (-12 °C)
05 14.0°F (-10 °C)
06 17.6 °F (-8 °C)
07 21.2 °F (-6 °C)
08 24.8 °F (-4 °C)
- 58 -