2-5. Details of control output function
¢
Operation status
Function
setting
External input and
output PCB
External output Output signal Status
Rotary switch
60-00 1, 2 Output of indoor unit CN47
Off  On Operation
On  Off Stop
1, B, C
External input and
output PCB
CN310
Off  On Operation
On  Off Stop
The output is low when the unit is stopped.
On
Off
On
Off
CN47
On
Off
CN310
Indoor unit operation
¢
Error status
Function
setting
External input and
output PCB
External output Output signal Status
Rotary switch
60-09 Output of indoor unit CN47
Off  On Error
On  Off Normal
2
External input and
output PCB
CN310
Off  On Error
On  Off Normal
1, C
External input and
output PCB
CN311
Off  On Error
On  Off Normal
The output is on when an error is generated for the indoor unit.
Error
Normal
On
Off
CN47
On
Off
CN310, 311, 312
Indoor unit
2-5. Details of control output function - (05-20) - 2. External input and output
FIELD
WORKING
FIELD
WORKING

Table of Contents

Other manuals for Fujitsu AOYG07KGCA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOYG07KGCA and is the answer not in the manual?

Fujitsu AOYG07KGCA Specifications

General IconGeneral
BrandFujitsu
ModelAOYG07KGCA
CategoryAir Conditioner
LanguageEnglish

Related product manuals