- 41 -
WALL MOUNTED
ASYG30, 36LMTA
2) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated
amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
3) Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting "00" (manufactur-
er’s recommended value).
Function number Setting value Setting description Factory setting
11
00 Standard (400 hours)
01 Long interval (1,000 hours)
02 Short interval (200 hours)
03 No indication
Function number Setting value Setting description
Factory
setting
30
(For cooling)
31
(For heating)
00 Standard setting
01 No correction 0.0 °C
02 -0.5 °C
More cooling
Less heating
03 -1.0 °C
04 -1.5 °C
05 -2.0 °C
06 -2.5 °C
07 -3.0 °C
08 -3.5 °C
09 -4.0 °C
10 +0.5 °C
Less cooling
More heating
11 +1.0 °C
12 +1.5 °C
13 +2.0 °C
14 +2.5 °C
15 +3.0 °C
16 +3.5 °C
17 +4.0 °C

Related product manuals