EasyManuals Logo

Fujitsu AOYG45KBTB User Manual

Fujitsu AOYG45KBTB
229 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #123 background imageLoading...
Page #123 background image
WARNING
Do not start operation until the refrigerant is charged completely. The compressor will fail if it is
operated before the refrigerant piping charging is complete.
Transmission cable between indoor unit and outdoor unit is 230 V.
Be sure not to remove thermistor sensor etc. from power wiring and connection wiring. Com-
pressor may fail if operated while removed.
Start wiring work after closing branch switch and over current breaker.
Use an earth leakage breaker that is capable of handing high frequencies. Because the outdoor
unit is inverter controlled, a high-frequency earth leakage breaker is necessary to prevent a mal-
function of the breaker itself.
When using an earth leakage breaker that has been designed solely for ground fault protection,
be sure to install a fuse-equipped switch or circuit breaker.
Do not connect the AC power supply to the transmission line terminal board. Improper wiring
can damage the entire system.
Do not use crossover power supply wiring for the outdoor unit.
If the temperature surrounding the breaker is too high, the amperage at which the breaker cuts
out may decrease.
- 115 -
4-1. Precaution for electrical wiring 4. Wiring design
SYSTEM
DESIGN
SYSTEM
DESIGN

Table of Contents

Other manuals for Fujitsu AOYG45KBTB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOYG45KBTB and is the answer not in the manual?

Fujitsu AOYG45KBTB Specifications

General IconGeneral
BrandFujitsu
ModelAOYG45KBTB
CategoryAir Conditioner
LanguageEnglish

Related product manuals