2-28. E: 94. Trip detection (Outdoor unit)
Indicator
Wired remote
controller
Error code E: 94
Check point 1. Check the outdoor unit fan operation, heat-exchanger, ambient temperature
No obstructions in air passages?
Heat exchange fins clogged
Outdoor unit fan motor check
Ambient temperature not raised by the effect of other heat sources?
Discharged air not sucked in?
Check point . Replace inverter PCB
If Check point do not improve the symptom, change inverter PCB.
Check point . Replace main PCB
If Check point do not improve the symptom, change main PCB.
Check point . Replace compressor
If Check point do not improve the symptom, change compressor.
End