2-29. E: 95. Compressor motor control error (Outdoor unit)
Indicator
Wired remote
controller
Error code E: 95
Check point 1. Check Noise from Compressor
Turn on Power and check operation noise.
→ If an abnormal noise show, replace compres-
sor.
↓
Check point 2. Check connection of around the compressor components
For compressor terminal, main PCB
• Check if connector is removed.
• Check erroneous connection.
• Check if cable is open. (Refer to inverter compressor in "Service parts information" on page 03-
52.)
→ Upon correcting the removed connector or mis-wiring, reset the power.
↓
Check point . Replace main PCB
If Check point do not improve the symptom, change main PCB.
↓
Check point . Replace compressor
If Check point do not improve the symptom, change compressor.
↓
End
2-29. E: 95. Compressor motor control error (Outdoor unit) - (03-34) - 2. Troubleshooting with error code
TROUBLESHOOTING