08-17
1. SW1 setting
DIP SWITCH SETTING
1-1 Low static pressure function setting
In case of installing in low static , you can minimize air flow and noise.
SW1-1 SW state
OFF Normal
ON Low static pressure
( Factory setting)
1-2 Dip SW 1-2,1-3,1-4 setting forbidden
SW1-2 OFF
SW1-3 OFF
SW1-4 OFF
( Factory setting)
2-1 Room temperature correct coefficient of heating.
Decide the heating temperature correct coefficient vale of heating.
Heat temperature correction
( Factory setting)
SW2-1 SW state
OFF +4 deg (Ceiling setting)
ON 0 deg (Room setting)
2-2 External input select edge/pulse
This switch is used to select the format of external input command
as shown in the table below.
( Factory setting)
SW2-2 SW state
OFF Edge
ON Pulse
2-3 Auto restart setting
Auto restart function can be selected by turning this switch ON/OFF.
AUTORESTART SETTING
( Factory setting)
SW2-3 SW state
OFF Validity
ON Invalidity
This switch can be used when group control system.
Set the indoor unit address in the 1,2,-,15 order.
ROTARY SWITCH SETTING
( Factory setting)
SW3 SW state
0 single
1-15 Indoor unit address