Type
Ceiling
Inverter heat pump
Model name ABYG36KRTA ABYG45KRTA
Power supply 230 V ~ 50 Hz
Power supply intake Outdoor unit
Available voltage range 198—264 V
Capacity
Cooling
Rated
kW 9.5 12.1
Btu/h 32,400 41,300
Min.—Max.
kW 2.8—11.2 4.0—13.5
Btu/h 9,600—38,200 13,600—46,000
Heating
Rated
kW 10.8 13.5
Btu/h 36,900 46,000
Min.—Max.
kW 2.7—12.7 4.2—16.2
Btu/h 9,200—43,300 14,300—55,300
Input power
Cooling
Rated
kW
2.96 4.22
Max. 4.52 4.79
Heating
Rated 2.88 3.84
Max. 4.31 4.81
Current
Cooling
Rated A
13.1 18.6
Heating 12.7 16.9
EER Cooling
kW/kW
3.21 2.87
COP Heating 3.75 3.52
Power factor
Cooling
%
98.9 99.0
Heating 98.8 98.9
Moisture removal L/h (pints/h) 2.6 (4.6) 4.5 (7.9)
Maximum operating current *
1
Cooling
A
22.6 28.5
Heating 22.6 28.5
Fan
Airflow rate
Cooling
HIGH
m
3
/h
1,850 1,900
MED 1,470 1,510
LOW 1,300 1,380
QUIET 1,050 1,130
Heating
HIGH 1,800 1,850
MED 1,470 1,510
LOW 1,300 1,380
QUIET 1,050 1,130
Type × Q'ty Sirocco × 4
Motor output W 110
Sound pressure level *
2
Cooling
HIGH
dB (A)
44 45
MED 40 41
LOW 37 39
QUIET 32 34
Heating
HIGH 44 45
MED 40 41
LOW 37 39
QUIET 32 34
Heat exchanger type
Dimensions (H × W × D) mm 294 × 1,335 × 39.9
Fin pitch mm 1.30
Rows × Stages 3 × 14
Pipe type Copper
Fin type Aluminum
Enclosure
Material Steel sheet
Color
White
Approximate color of Munsell N9.25/
Dimensions
(H × W × D)
Net
mm
235 × 1,700 × 705
Gross 330 × 1,785 × 825
Weight
Net
kg
38
Gross 48
Connection pipe
Size
Liquid
mm (in)
Ø9.52 (Ø3/8)
Gas Ø15.88 (Ø5/8)
Method Flare
Drain hose
Material PVC
Tip diameter mm Ø25 (I.D.), Ø32 (O.D.)
Operation range
Cooling
°C 18 to 32
%RH 80 or less
Heating °C 16 to 30
Remote controller (Option)
Wired remote controller, Wireless remote controller, Mobile app*3 (FGLair
™
)
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Maximum current is maximum value when operated within the operation range.
• *2: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• *3: Available on Google Play
™
store or on App Store
®
. Optional WLAN adapter is also required. For details, refer to the setting manual.
• This data is based on EN 14511 standard.
- 6 -
1. Specifications
CEILING TYPE
ABYG18-45KRTA
CEILING TYPE