03-02
1-5. Setting the Room temperature sensor switching
(Only for Wired remote controller)
When using the Wired remote controller temperture sensor, change the setting to "Both" (01).
( Factory setting)
Setting Description
Function Number Setting Value
Indoor unit
Both
42
00
01
* 00 : Sensor on the indoor unit is active.
* 01 : Sensors on both indoor unit and wired remote controller is active.
1-6. Setting the Remote controller signal code
(Only for wireless remote controller)
The indoor unit signal code can be changed. Select the appropriate signal code.
( Factory setting)
Setting Description
Function Number Setting Value
A
B
C
D
44
00
01
02
03
1-7. Setting the External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
( Factory setting)
Setting Description
Function Number Setting Value
Operation /Stop mode
(Setting prohibited)
Forced stop mode
46
00
01
02
( Factory setting)
Setting Description
Function Number Setting Value
Disable
Enable
49
00
01
1-8. Setting the Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation
when the outdoor unit is stopped during cooling operation.
* If setting value is "00" :
When the outdoor unit is stopped, the indoor unit fan operates continuously
following the setting on the remote controller.
* If setting value is "01" :
When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low speed.