EasyManua.ls Logo

Fujitsu ASU 9RLF1

Fujitsu ASU 9RLF1
61 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5. INDOOR FAN CONTROL
The airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH,
while the indoor fan only runs.
When Fan mode is set at (Auto), it operates on (MED) Fan Speed.
01-04
1. Fan speed
2. FAN OPERATION
( Table 4 : Indoor Fan Speed )
Operation mode Air flow mode
Speed (rpm)
1320
1280
1160
980
Cooling/ Fan
Hi
Hi
710
600
480
1320
Me+
Me
Me
Heating
Lo
Lo
1160
930
Quiet
Quiet
680
Dry
S-Lo
X zone: 680
J zone: 660
Cool air prevention
3. COOLING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature,
as shown in Fig. 3.
On the other hand, if switched in [HIGH] [QUIET], the indoor motor will run at a constant airflow of [COOL]
operation modes QUIET, LOW, MED, HIGH,as shown in Table 4.
( Fig. 3 : Airflow change - over ( Cooling : AUTO ) )
When the room
temperature rises
When the room
temperature drops
TR : Room temperature
Ts : Setting temperature
TR-Ts > 4°F
(2°C)
2°F > TR-Ts
(1°C)
4°F > TR-Ts > 2°F
(2°C) (1°C)
=
TR-Ts > 5°F
(2.5°C)
=
3°F > TR-Ts
(1.5°C)
5°F > TR-Ts > 3°F
(2.5°C) (1.5°C)
=
Hi mode
Me mode
Lo mode
ASU9RLF1 ASU12RLF1
4. DRY OPERATION
Refer t
o t
h
e T
a
bl
e
4.
During
the
d
ry mod
e
o
perat
ion
,
t
he
f
an speed setting can not be ch
a
ng
e
d.
Poweful
1380
Poweful
1380
*Soft Quiet
600
*Note, during Economy operation and operation mode is Fan, air flow is 1 step downs.
(Hi > Me, Me > Lo, Lo > Quiet, Quiet > Soft Quiet)