01-31
Check run judgment failure display
If check run cannot be performed, the following is displayed. In this case, the check
run will stop. Please check by using the cooling test run of the indoor unit.
Temperature out of range judgment
(2-blink)
blink
(High-speed)
FEDC
MONITOR
ERROR
BA
POWER
MODE
Wiring / piping number difference
FEDC
MONITOR
ERROR
BA
POWER
MODE
blink
(High-speed)
blink
(High-speed)
OR
(2-blink)
(2-blink)
Re-display check run results
If you wish to check the automatic wiring correction contents, by briefly pressing the
"CHECK" switch, the check run results is displayed. Please check the check run
results by referring to the result table in step (4) of "8.3. Operating procedure for check run".
If the automatic wiring correction contents has not been done, the POWER/MODE
LED will blink twice and the MONITOR LED will turn off.
Automatic wiring correction memory reset
CAUTION
When relocating the unit, reset the memory beforehand, or the unit may not function
normally.
(1) Press the "CHECK" switch.
The LED will light as shown in “8.5 Re-display check run results”.
(2) Press the "CHECK" switch for more than 3 seconds when the LED is on.
(3) The LEDs from A to F will light in sequence, and then all LEDs will light to indicate
the completion of the Automatic wiring correction memory reset.
(4) Disconnect the power supply or turn off the breaker.

Table of Contents

Other manuals for Fujitsu ASU18RLF

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASU18RLF and is the answer not in the manual?

Fujitsu ASU18RLF Specifications

General IconGeneral
BrandFujitsu
ModelASU18RLF
CategoryAir Conditioner
LanguageEnglish

Related product manuals