10. Electrical characteristics
Model name AOUH18LMAS1 AOUH24LMAS1
Power supply
Voltage V 208/230
Frequency Hz 60
MCA *
1
A 17.1 19.6
Starting current A 7.0 8.3
Wiring spec.
*
2
MAX. CKT. BKR *
3
A 20
Power cable AWG 14 12
Connection
cable *
4
Size AWG 14
Limited wiring
length
ft (m) 167 (51)
*
1
: Minimum Circuit Ampacity (Calculation based on UL60335-2-40)
*
2
: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate de-
vices complied to the regional standard.
*
3
: Maximum Circuit Breaker
*
4
: Limit voltage drop to less than 2%. If voltage drop is 2% or more, increase cable conductor size.
- 81 -