3. INDOOR FAN CONTROL
1. Fan speed
( Table 2 : Indoor Fan Speed )
01-02
Operation mode Air flow mode Speed (rpm)
Hi 1220
1100
920
680
Me
Lo
Dry
(Refer Fig 2)
Monitoring
Quiet
Hi
Me
Lo
Quiet
1160
1100
980
700
600
480
Cool air prevention
S- Lo
Cooling
Heating
ASYA07/09LBCM
Me+
1220
X zone : 680
J zone : 650
Y zone : 0 480
ASYA12LBCM
Operation mode Air flow mode Speed (rpm)
Hi 1440
1200
920
680
Me
Lo
Dry
(Refer Fig 2)
Monitoring
Quiet
Hi
Me
Lo
Quiet
1370
1200
980
700
600
480
Cool air prevention
S- Lo
Cooling
Heating
Me+
1440
X zone : 680
J zone : 650
Y zone : 0 480
2. FAN OPERATION
The airflow can be switched in 6 steps such as AUTO, QUIET, LOW, MED, MED+, HIGH,
while the indoor fan only runs.
3. COOLING OPERATION
(Fig.1)
airflow change - over ( Cooling: AUTO )
When the room
temperature rises
Lo mode
When the room
temperature lowers
Hi mode
Me mode
TR : Room temperature
Ts : Setting temperature
TR-Ts > 2 degC
=
1 degC > TR-Ts
2 degC > TR-Ts > 1 degC
=
TR-Ts > 2.5 degC
=
1.5 degC > TR-Ts
2.5 degC > TR-Ts > 1.5 degC
=
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature,
as shown in Figure 1.
On the other hand, if switched in [HIGH] [QUIET], the indoor motor will run at a constant airflow of [COOL]
operation modes QUIET, LOW, MED, HIGH,as shown in Table 2.