EasyManuals Logo

Fujitsu ASYG09LUCA User Manual

Fujitsu ASYG09LUCA
413 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #78 background imageLoading...
Page #78 background image
3. OUTDOOR UNIT & BRANCH BOX
SAFETY DEVICES9.
OUTDOOR UNIT9-1.
Safety device AO
îš¾
G45LBT8
Fuse
Main PCB AC 250V 3.15A
INV PCB DC 400V 5A
Filter
AC 250V 10A
AC 250V 3.15A
Protector Filter AC 500V 50A
Compressor Protector
Overcurrent protection -
Temperature protection Off : 115°C On : 70°C
High Pressure Protection Off : 4.2MPa On : 3.2MPa
Low Pressure Protection Off : 0.05MPa
BRANCH BOX9-2.
Safety device UTP-PY03A, UTP-PY02A
Fuse PCB
AC 250V 3.15A x 2
AC 250V 10A x 1
- (03 - 20) -