6. Capacity compensation rate for pipe length and height
difference
Height difference H
Indoor unit is higher than outdoor unit *
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H H
6-1. Model: AOYG18KMTA
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 15 20 25
Height difference H (m)
Indoor unit is higher than
outdoor unit *
1
20 — — — — 0.917 0.900
10 — — 0.966 0.947 0.932 0.914
7.5 — 0.979 0.970 0.951 0.936 0.918
5 0.992 0.983 0.974 0.955 0.939 0.922
0 1.000 0.991 0.981 0.963 0.946 0.930
Indoor unit is lower than
outdoor unit *
2
-5 1.000 0.991 0.981 0.963 0.946 0.930
-7.5 — 0.991 0.981 0.963 0.946 0.930
-10 — — 0.981 0.963 0.946 0.930
-20 — — — — 0.946 0.930
HEATING
Pipe length (m)
5 7.5 10 15 20 25
Height difference H (m)
Indoor unit is higher than
outdoor unit *
1
20 — — — — 0.887 0.871
10 — — 0.952 0.903 0.887 0.871
7.5 — 0.976 0.952 0.903 0.887 0.871
5 1.000 0.976 0.952 0.903 0.887 0.871
0 1.000 0.976 0.952 0.903 0.887 0.871
Indoor unit is lower than
outdoor unit *
2
-5 0.995 0.971 0.947 0.899 0.883 0.866
-7.5 — 0.969 0.945 0.897 0.881 0.865
-10 — — 0.942 0.894 0.879 0.863
-20 — — — — 0.869 0.854
- 53 -
6-1. Model: AOYG18KMTA 6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOYG18-24KMTA
OUTDOOR UNIT
AOYG18-24KMTA