- (01 - 06) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
SPECIFICATIONS3.
Note :
Specications are based on the following conditions.
Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/24 °CWB.
Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
The maximum current is the maximum value when operated within the operation range (temperature)
Type
CASSETTE MODEL
INVERTER HEATPUMP
Model name
Indoor unit AU
A45LCLU
Outdoor unit
AO
A45LBTL
Power source 230V ~ 50Hz
Available voltage range 198-264V ~ 50Hz
European energy label
Cooling A
Heating A
Capacity
Cooling
Rated
kW 12.5
BTU/h 42700
Min-Max
kW 4.0-14.0
BTU/h 13700-47800
Heating
Rated
kW 14.0
BTU/h 47800
Min-Max
kW 4.2-16.2
BTU/h 14300-55300
Input power
Cooling
Rated
kW
3.89
Max 4.56
Heating
Rated 3.77
Max 4.56
Current
Cooling
Rated
A
17.0
Max 20.0
Heating
Rated 16.5
Max 20.0
EER Cooling
kW/kW
3.21
COP Heating 3.71
Moisture removal l/h (pints/h) 4.5(7.9)
Fan
Airow
rate
Cooling
High
m
3
/h
1900
Med 1640
Low 1460
Quiet 1250
Heating
High 1900
Med 1640
Low 1460
Quiet 1250
Type × Q'ty Turbo × 1
Motor output W 80
Sound pressure level
Cooling
High
dB(A)
46
Med 42
Low 40
Quiet 36
Heating
High 46
Med 42
Low 40
Quiet 36
Heat exchanger type
Dimensions (H × W × D)
mm
252×2021×13.3
252×2087×13.3
252×2153×13.3
Fin pitch 1.3
Rows x Stages 3 x 12
Pipe type Copper
Fin type Aluminium
Enclosure (Panel)
Material Steel (HIPS)
Colour
WHITE
Approximate colour of MUNSELL N 9.25/
Dimensions
( H×W×D)
Net
Unit
mm
288×840×840
Panel 50×950×950
Gross
Unit 360×960×985
Panel 115×1120×1000
Weight
Net
Unit
kg(lbs.)
27(60)
Panel 5.5(12)
Gross
Unit 33(73)
Panel 8.5(19)
Connection pipe
Size
Liquid
mm
Ø 9.52 (3/8 in.)
Gas Ø 15.88 (5/8 in.)
Method Flare
Operation range
Cooling
°C 18 to 32
%RH 80 or less
Heating °C 16 to 30
Remote controller type Wired
Drain pipe
Material PVC(VP25)
Size mm Outer diameter : 32.0 / Inner diameter : 25.0