When function setting is “Forced stop” mode
In the case of “Edge” input:
Function
setting
Rotary SW on External
input and output PCB
External input Input signal Command
46-02 1
External input and
output PCB
CN313
Off → On Forced stop
On → Off Normal
On
Off
Forced stop
Normal
Operation
Stop
Remote controller
On On
Indoor unit
On
CN313
In the case of “Pulse” input:
Function
setting
Rotary SW on External
input and output PCB
External input Input signal Command
46-02 1
External input and
output PCB
CN313 Pulse Forced stop
CN314 Pulse Normal
On
Off
Operation
Stop
Remote controller
On
Off
Forced stop
Normal
CN313
CN314
On On On
Indoorunit
NOTES:
When the forced stop is triggered, indoor unit stops and Operation/Stop operation by the re-
mote controller is restricted.
When forced stop function is used with forming a remote controller group, connect the same
equipment to each indoor unit within the group.
- 197 -
11-4. Wall mounted type (KGTE, KMTE, KMCE, KETE, and KETE-B) 11. External input and output
4-5 UNIT
MULTI-SPLIT TYPE
4-5 UNIT
MULTI-SPLIT TYPE

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AUXG07-22KVLA and is the answer not in the manual?

Fujitsu AUXG07-22KVLA Specifications

General IconGeneral
BrandFujitsu
ModelAUXG07-22KVLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals