Details of function
Control input function
• When function setting is “Operation/Stop” mode 1
– In the case of “Edge” input:
Function
setting
Rotary SW on External
input and output PCB
External input Input signal Command
46-00 1
External input and
output PCB
CN313
Off → On Operation
On → Off Stop
Operation
Stop
Remote controller
On
Off
Indoor unit
On
CN313
– In the case of “Pulse” input:
Function
setting
Rotary SW on External
input and output PCB
External input Input signal Command
46-00 1
External input and
output PCB
CN313 Pulse Operation
CN314 Pulse Stop
On
On
Off
Operation
Stop
Remote controller
On
Off
Indoor unit
CN313
CN314
NOTES:
• The last command has priority.
• The indoor units within the same remote controller group operates in the same mode.