Loading...
¢ Indoor unit: 12,000 Btu/h
Cooing
Pipe length
m 2.5 5 10 15 20
Height difference H (m)
Indoor unit is higher than outdoor
unit *1
15 0.919 0.883
10 0.962 0.926 0.891
5 0.991 0.969 0.933 0.897
2.5 0.993 0.993 0.971 0.935 0.899
0 1.000 1.000 0.978 0.941 0.905
Indoor unit is lower than outdoor
unit *2
-2.5 1.000 1.000 0.978 0.941 0.905
-5 1.000 0.978 0.941 0.905
-10 0.978 0.941 0.905
-15 0.941 0.905
Heating
Pipe length
m 2.5 5 10 15 20
Height difference H (m)
Indoor unit is higher than outdoor
unit *1
15 0.941 0.924
10 0.958 0.941 0.924
5 1.000 0.958 0.941 0.924
2.5 0.992 1.000 0.958 0.941 0.924
0 0.992 1.000 0.958 0.941 0.924
Indoor unit is lower than outdoor
unit *2
-2.5 0.988 0.996 0.954 0.937 0.920
-5 0.994 0.952 0.935 0.918
-10 0.948 0.932 0.915
-15 0.927 0.910
¢ Indoor unit: 14,000 Btu/h
Cooing
Pipe length
m 2.5 5 10 15 20
Height difference H (m)
Indoor unit is higher than outdoor
unit *1
15 0.913 0.873
10 0.959 0.919 0.882
5 0.991 0.967 0.927 0.888
2.5 0.993 0.993 0.969 0.929 0.890
0 1.000 1.000 0.976 0.934 0.895
Indoor unit is lower than outdoor
unit *2
-2.5 1.000 1.000 0.976 0.934 0.895
-5 1.000 0.976 0.934 0.895
-10 0.976 0.934 0.895
-15 0.934 0.895
Heating
Pipe length
m 3 7.5 10 15 20
Height difference H (m)
Indoor unit is higher than outdoor
unit *1
15 0.940 0.924
10 0.957 0.940 0.924
5 1.000 0.957 0.940 0.924
2.5 0.993 1.000 0.957 0.940 0.924
0 0.993 1.000 0.957 0.940 0.924
Indoor unit is lower than outdoor
unit *2
-2.5 0.989 0.996 0.953 0.936 0.920
-5 0.994 0.951 0.934 0.918
-10 0.947 0.932 0.915
-15 0.926 0.910
- 282 -
7-2. Model: AOYG18KBTA2 7. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOYG14-18KBTA2
OUTDOOR UNIT
AOYG14-18KBTA2

Table of Contents