1-2. Outdoor unit
Type Inverter heat pump
Model name AOYG09KATA AOYG12KATA AOYG14KATA
Power supply 230 V ~ 50 Hz
Available voltage range 198—264 V
Starting current A 4.4 5.8 6.6
Fan
Airflow rate
Cooling
m
3
/h
1,610 1,630 1,670
Heating 1,550 1,410 1,580
Type × Q'ty Propeller fan × 1
Motor output W 23
Sound pressure level *1
Cooling
dB (A)
47 49 50
Heating 48 50 51
Sound power level
Cooling
dB (A)
60 62 63
Heating 60 62 63
Heat exchanger type
Dimensions
(H × W × D)
mm
504 × 650 × 18.19
Main 1: 504 × 630 × 18.19
Main 2: 504 × 630 × 18.19
Main 1: 504 × 881 × 18.19
Main 2: 504 × 851 × 18.19
Fin pitch 1.3
Main 1: 1.3
Main 2: 1.3
Rows × Stages 1 × 24
Main 1: 1 × 24
Main 2: 1 × 24
Pipe type Copper
Fin type
Type (Material) Aluminum
Surface treatment PC fin
Compressor
Type × Q'ty DC rotary × 1
Motor output W 550 900
Refrigerant
Type (Global warming potential) R32 (675)
Charge g 600 700 850
Refrigerant oil
Type RB74AF RB68A
Amount
cm
3
240 340
Enclosure
Material Steel sheet
Color
Beige
Approximate color of Munsell 10YR 7.5/1.0
Dimensions
(H × W × D)
Net
mm
541 × 663 × 290 542 × 799 × 290
Gross 602 × 804 × 375 602 × 940× 375
Weight
Net
kg
23 25 32
Gross 27 29 36
Connection pipe
Size
Liquid
mm (in)
Ø 6.35 (Ø 1/4)
Gas Ø 9.52 (Ø 3/8)
Method Flare
Pre-charge length
m
15
Max. length 15 20
Max. height difference 15
Operation range
Cooling
°C
-10 to 46
Heating -15 to 24
Drain hose
Material PP
Size mm Ø 13.0 (I. D.), Ø 16.0 to Ø 16.8 (O. D.)
NOTES:
Specifications are based on the following conditions:
Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length: 5.0 m, Height difference: 0 m.
Protective function might work when using it outside the operation range.
*1: Sound pressure level
Measured values in manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
1-2. Outdoor unit
- (01-5) - 1. Specifications
GENERAL
INFORMATION
GENERAL
INFORMATION

Other manuals for Fujitsu AUXG09KVLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AUXG09KVLA and is the answer not in the manual?

Fujitsu AUXG09KVLA Specifications

General IconGeneral
BrandFujitsu
ModelAUXG09KVLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals