1. Specifications
1-1. Indoor unit
Type
Cassette
Inverter heat pump
Model name AUXG09KVLA AUXG12KVLA AUXG14KVLA
Power supply 230 V ~ 50 Hz
Power supply intake Outdoor unit
Available voltage range 198—264 V
Capacity
Cooling
Rated
kW 2.50 3.50 4.30
Btu/h 8,500 11,900 14,700
Min.—Max.
kW 0.90—2.70 0.90—3.70 0.90—4.50
Btu/h 3,100—9,200 3,100—12,600 3,100—15,300
Heating
Rated
kW 3.20 4.10 5.00
Btu/h 10,900 13,400 17,000
Min.—Max.
kW 0.90—3.90 0.90—4.40 0.90—5.30
Btu/h 3,100—13,300 3,100—15,000 3,100—18,000
Input power
Cooling
Rated
kW
0.68 1.09 1.37
Max. 1.59 1.78 2.12
Heating
Rated 0.88 1.17 1.42
Max. 1.59 1.78 2.12
Current
Cooling
Rated A
3.4 5.2 6.4
Heating 4.4 5.8 6.6
Power factor
Cooling
%
87.0 91.1 93.1
Heating 87.0 87.7 93.5
EER Cooling
kW/kW
3.68 3.21 3.14
COP Heating 3.64 3.50 3.52
Moisture removal L/h (pints/h) 0.6 (1.1) 1.2 (2.1) 1.5 (2.6)
Maximum operating current *1
Cooling
A
6.9 7.7 9.2
Heating 6.9 7.7 9.2
Fan
Airflow rate
Cooling
HIGH
m
3
/h
540 600 680
MED 490 530 580
LOW 440 470 490
QUIET 390 410 410
Heating
HIGH 540 600 800
MED 490 530 680
LOW 440 470 580
QUIET 390 410 450
Type × Q'ty Turbo × 1
Motor output W 54
Sound pressure level *2
Cooling
HIGH
dB (A)
33 37 38
MED 31 34 34
LOW 29 30 30
QUIET 27 27 27
Heating
HIGH 34 37 43
MED 32 34 38
LOW 29 31 34
QUIET 27 29 30
Heat exchanger type
Dimensions
(H × W × D)
mm
Main 1: 210 × 1,310 × 13.3
Main 2: 210 × 1,250 × 13.3
Fin pitch
Main 1: 1.2
Main 2: 1.2
Rows × Stages
Main 1: 1 × 10
Main 2: 1 × 10
Pipe type Copper tube
Fin type Aluminum
Dimensions
(H × W × D)
Net
mm
245 × 570 × 570
Gross 265 × 730 × 625
Weight
Net
kg
15
Gross 19
Connection pipe
Size
Liquid
mm (in)
Ø 6.35 (Ø 1/4)
Gas Ø 9.52 (Ø 3/8)
Method Flare
Operation range
Cooling
°C 18 to 32
%RH 80 or less
Heating °C 16 to 30
Cassette grille
(Grid type: Option)
Material Polystyrene
Color
White
Approximate color of Munsell 9PB 9.1/0.2
Dimensions
(H × W × D)
Net
mm
49 × 620 × 620
Gross 120 × 765 × 755
Weight
Net
kg
2.3
Gross 4.5
Remote control (Option)
Wired remote controller, Wireless remote controller, Mobile app*3 (FGLair
™
)
Drain hose
Material PVC
Size mm VP25 [Ø 25 (I.D.), Ø 32 (O.D.)]
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 5.0 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Maximum operating current is the total current of the indoor unit and the outdoor unit.
• *2: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• *3: Available on Google Play
™
store or on App Store
®
. Optional WLAN adapter is also required. For details, refer to the setting manual.
1-1. Indoor unit
- (01-1) - 1. Specifications
GENERAL
INFORMATION
GENERAL