Type
Cassette
Inverter heat pump
Model name AUXG18KVLA AUXG22KVLA
Power supply 230 V ~ 50 Hz
Power supply intake Outdoor unit
Available voltage range 198—264 V
Capacity
Cooling
Rated
kW 5.20 6.00
Btu/h 17,700 20,500
Min.—Max.
kW 0.90—5.40 0.90—6.30
Btu/h 3,100—18,400 3,100—21,400
Heating
Rated
kW 6.00 7.00
Btu/h 20,500 23,900
Min.—Max.
kW 0.90—6.30 0.90—7.40
Btu/h 3,100—21,400 3,100—25,200
Input power
Cooling
Rated
kW
1.69 1.95
Max. 2.33 2.67
Heating
Rated 1.72 2.00
Max. 2.33 2.67
Current
Cooling
Rated A
7.8 8.6
Heating 7.9 8.8
Power factor
Cooling
%
94.2 98.6
Heating 94.7 98.8
EER Cooling
kW/kW
3.08 3.08
COP Heating 3.49 3.50
Moisture removal L/h (pints/h) 2.2 (3.9) 2.6 (4.6)
Maximum operating current *1
Cooling
A
10.1 11.6
Heating 10.1 11.6
Fan
Airflow rate
Cooling
HIGH
m
3
/h
680 830
MED 580 740
LOW 490 600
QUIET 410 450
Heating
HIGH 800 860
MED 680 760
LOW 580 700
QUIET 450 530
Type × Q'ty Turbo × 1
Motor output W 54
Sound pressure level *2
Cooling
HIGH
dB (A)
38 44
MED 34 42
LOW 30 36
QUIET 26 30
Heating
HIGH 43 45
MED 38 43
LOW 34 40
QUIET 30 33
Heat exchanger type
Dimensions
(H × W × D)
mm
Main 1: 210 × 1,310 × 13.3
Main 2: 210 × 1,250 × 13.3
Main 1: 210 × 1,360 × 13.3
Main 2: 210 × 1,295 × 13.3
Main 3: 210 × 1,235 × 13.3
Fin pitch
Main 1: 1.2
Main 2: 1.2
Main 1: 1.45
Main 2: 1.45
Main 2: 1.45
Rows × Stages
Main 1: 1 × 10
Main 2: 1 × 10
Main 1: 1 × 10
Main 2: 1 × 10
Main 3: 1 × 10
Pipe type Copper tube
Fin type Aluminum
Dimensions
(H × W × D)
Net
mm
245 × 570 × 570
Gross 265 × 730 × 625
Weight
Net
kg
15 16
Gross 19 20
Connection pipe
Size
Liquid
mm (in)
Ø 6.35 (Ø 1/4)
Gas Ø 12.70 (Ø 1/2)
Method Flare
Operation range
Cooling
°C 18 to 32
%RH 80 or less
Heating °C 16 to 30
Cassette grille
(Grid type: Option)
Material Polystyrene
Color
White
Approximate color of Munsell 9PB 9.1/0.2
Dimensions
(H × W × D)
Net
mm
49 × 620 × 620
Gross 120 × 765 × 755
Weight
Net
kg
2.3
Gross 4.5
Remote control (Option)
Wired remote controller, Wireless remote controller, Mobile app*3 (FGLair
)
Drain hose
Material PVC
Size mm VP25 [Ø 25(I.D.), Ø 32(O.D.)]
NOTES:
Specifications are based on the following conditions:
Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length: 5.0 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
Protective function might work when using it outside the operation range.
*1: Maximum operating current is the total current of the indoor unit and the outdoor unit.
*2: Sound pressure level:
Measured values in manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
*3: Available on Google Play
store or on App Store
®
. Optional WLAN adapter is also required. For details, refer to the setting manual.
1-1. Indoor unit
- (01-3) - 1. Specifications
GENERAL
INFORMATION
GENERAL
INFORMATION

Other manuals for Fujitsu AUXG09KVLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AUXG09KVLA and is the answer not in the manual?

Fujitsu AUXG09KVLA Specifications

General IconGeneral
BrandFujitsu
ModelAUXG09KVLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals