4. Capacity table
Capacity tables show each of following values calculated based on the outdoor temperature and the
indoor temperature, under given Airflow Rate (AFR):
For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP)
For heating capacity: Total Capacity (TC) and Input Power (IP)
4-1. Cooling capacity
¢
Model: AUXG18KRLB
AFR
m
3
/h
1,050
Indoor temperature
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW kW
-15 4.17 3.69 0.41 4.65 3.71 0.42 4.80 4.03 0.42 5.12 4.05 0.43 5.28 4.37 0.43 5.60 4.35 0.43 5.91 4.64 0.44
-10 4.20 3.71 0.36 4.68 3.74 0.36 4.84 4.06 0.36 5.16 4.07 0.37 5.32 4.40 0.37 5.64 4.38 0.37 5.96 4.67 0.38
0 3.99 3.62 0.55 4.44 3.64 0.56 4.60 3.96 0.56 4.90 3.97 0.57 5.05 4.29 0.57 5.35 4.27 0.58 5.66 4.55 0.58
5 3.91 3.60 0.59 4.36 3.62 0.60 4.50 3.93 0.60 4.80 3.94 0.61 4.95 4.26 0.61 5.25 4.24 0.62 5.54 4.52 0.62
10 4.05 3.65 0.40 4.51 3.68 0.40 4.67 4.00 0.40 4.98 4.01 0.41 5.13 4.33 0.41 5.44 4.31 0.41 5.75 4.59 0.42
15 3.92 3.61 0.49 4.36 3.63 0.50 4.51 3.95 0.50 4.81 3.96 0.51 4.96 4.28 0.51 5.26 4.26 0.52 5.56 4.54 0.52
20 4.83 3.99 0.94 5.39 4.02 0.95 5.57 4.37 0.96 5.94 4.38 0.97 6.12 4.73 0.97 6.49 4.71 0.98 6.85 5.02 0.99
25 4.59 3.83 1.07 5.11 3.85 1.09 5.29 4.19 1.09 5.64 4.20 1.10 5.81 4.54 1.11 6.16 4.52 1.12 6.51 4.82 1.13
30 4.35 3.69 1.20 4.84 3.71 1.22 5.01 4.03 1.22 5.34 4.05 1.23 5.50 4.37 1.24 5.83 4.35 1.25 6.16 4.64 1.26
35 4.11 3.53 1.31 4.58 3.55 1.33 4.73 3.86 1.34 5.04 3.87 1.35 5.20 4.18 1.36 5.51 4.16 1.37 5.82 4.43 1.39
40 3.68 3.44 1.21 4.10 3.46 1.23 4.24 3.77 1.23 4.52 3.78 1.24 4.66 4.08 1.25 4.94 4.06 1.26 5.22 4.33 1.28
46 2.58 2.58 0.90 2.87 2.77 0.91 2.97 2.97 0.92 3.16 3.02 0.93 3.26 3.26 0.93 3.46 3.25 0.94 3.65 3.46 0.95
¢
Model: AUXG22KRLB
AFR
m
3
/h
1,050
Indoor temperature
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW kW
-15 4.99 3.86 0.55 5.56 3.88 0.56 5.75 4.22 0.56 6.13 4.23 0.57 6.32 4.57 0.57 6.70 4.55 0.58 7.08 4.85 0.58
-10 5.03 3.87 0.46 5.61 3.89 0.47 5.80 4.23 0.47 6.18 4.24 0.48 6.37 4.58 0.48 6.75 4.56 0.48 7.13 4.86 0.49
0 4.91 3.81 0.47 5.46 3.83 0.48 5.65 4.16 0.48 6.02 4.18 0.49 6.21 4.51 0.49 6.58 4.49 0.49 6.96 4.79 0.50
5 4.77 3.76 0.60 5.32 3.78 0.61 5.50 4.11 0.61 5.86 4.12 0.62 6.04 4.45 0.62 6.40 4.43 0.63 6.76 4.72 0.63
10 4.74 3.75 0.59 5.28 3.77 0.60 5.46 4.10 0.60 5.82 4.11 0.61 6.00 4.44 0.61 6.36 4.42 0.62 6.72 4.71 0.62
15 4.59 3.68 0.70 5.11 3.70 0.72 5.29 4.02 0.72 5.64 4.04 0.73 5.81 4.36 0.73 6.16 4.34 0.74 6.51 4.63 0.74
20 5.77 4.20 1.25 6.43 4.23 1.27 6.65 4.60 1.28 7.09 4.61 1.29 7.31 4.98 1.30 7.75 4.96 1.31 8.19 5.28 1.33
25 5.43 4.07 1.39 6.05 4.09 1.41 6.25 4.45 1.42 6.66 4.46 1.43 6.87 4.82 1.44 7.28 4.80 1.45 7.69 5.11 1.47
30 5.08 3.93 1.52 5.66 3.96 1.55 5.85 4.30 1.56 6.24 4.32 1.57 6.43 4.66 1.58 6.82 4.64 1.60 7.20 4.94 1.61
35 4.74 3.80 1.65 5.28 3.82 1.68 5.46 4.15 1.68 5.82 4.17 1.70 6.00 4.50 1.71 6.36 4.48 1.73 6.72 4.77 1.74
40 4.50 3.68 1.79 5.01 3.70 1.81 5.18 4.02 1.82 5.52 4.04 1.84 5.69 4.36 1.85 6.03 4.34 1.87 6.37 4.63 1.89
46 3.69 3.26 1.54 4.11 3.28 1.57 4.25 3.56 1.57 4.53 3.57 1.59 4.67 3.86 1.60 4.95 3.84 1.61 5.23 4.10 1.63
- 8 -
4-1. Cooling capacity
4. Capacity table
CASSETTE TYPE
AUXG18, 22KRLB
CASSETTE TYPE
AUXG18, 22KRLB