2-2. Installation space requirement
Provide sufficient installation space for product safety.
For 4-direction setting:
1,500
or more
1,000 or more
1,800 or more
Obstruction
3,000 or more
Strong and durable ceiling
Floor
Ceiling height
Ceiling mode* “Low” : 2.7 m or less
Ceiling mode “Standard” : up to 3.0 m
Ceiling mode “High” : up to 3.5 m
256 or more
Unit: mm
*: For switching the ceiling mode, refer to "Contents of function setting" on page 34.
For 3-direction setting:
NOTES:
• To set “3-direction”, optional Air outlet shutter plate (UTR-YDZK) must be installed, and the “out-
let-direction” need to be switched to “3-way” by remote controller.
*: When installing the indoor unit, be careful about the maintenance space.
• The ceiling height cannot be set in the 3-way outlet mode. Therefore, ceiling height setting
change by function setting 20 is prohibited. For details, refer to "Contents of function setting" on
page 34.
- 5 -
2-2. Installation space requirement
2. Dimensions
CASSETTE TYPE
AUXG18, 22KRLB
CASSETTE TYPE
AUXG18, 22KRLB