4-2. Heating capacity
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
¢
Model: AUXG18KRLB
AFR
m
3
/h
1,050
Indoor temperature
°CDB 16 18 20 22 24
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-15 -16 5.05 1.66 4.93 1.70 4.81 1.73 4.69 1.76 4.57 1.80
-10 -11 5.69 1.77 5.56 1.80 5.42 1.84 5.28 1.88 5.15 1.91
-5 -7 6.33 1.87 6.18 1.91 6.03 1.95 5.88 1.99 5.73 2.03
0 -2 6.97 1.99 6.81 2.03 6.64 2.07 6.47 2.11 6.31 2.15
5 3 7.61 2.08 7.43 2.13 7.25 2.17 7.07 2.21 6.89 2.26
7 6 7.88 2.12 7.69 2.17 7.50 2.21 7.31 2.25 7.13 2.30
10 8 8.51 2.21 8.30 2.25 8.10 2.30 7.90 2.35 7.70 2.39
15 10 8.46 1.95 8.26 1.99 8.06 2.03 7.86 2.07 7.66 2.10
20 15 7.96 1.54 7.77 1.57 7.58 1.60 7.39 1.63 7.20 1.66
24 18 8.40 1.53 8.20 1.56 8.00 1.59 7.80 1.62 7.60 1.65
¢
Model: AUXG22KRLB
AFR
m
3
/h
1,050
Indoor temperature
°CDB 16 18 20 22 24
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-15 -16 5.60 2.10 5.46 2.15 5.33 2.19 5.20 2.23 5.06 2.28
-10 -11 6.14 2.19 6.00 2.23 5.85 2.28 5.70 2.33 5.56 2.37
-5 -7 6.70 2.27 6.54 2.31 6.38 2.36 6.22 2.41 6.06 2.45
0 -2 7.26 2.33 7.08 2.38 6.91 2.43 6.74 2.48 6.56 2.53
5 3 7.81 2.41 7.63 2.46 7.44 2.51 7.25 2.56 7.07 2.61
7 6 8.40 2.41 8.20 2.46 8.00 2.51 7.80 2.56 7.60 2.61
10 8 8.05 2.28 7.86 2.32 7.67 2.37 7.48 2.42 7.29 2.46
15 10 7.49 2.05 7.31 2.10 7.13 2.14 6.95 2.18 6.77 2.21
20 15 7.04 1.75 6.87 1.78 6.70 1.82 6.53 1.86 6.37 1.88
24 18 7.32 1.73 7.14 1.76 6.97 1.80 6.80 1.84 6.62 1.86
- 9 -
4-2. Heating capacity
4. Capacity table
CASSETTE TYPE
AUXG18, 22KRLB
CASSETTE TYPE
AUXG18, 22KRLB