1. Specifications
Type
Cassette
Inverter heat pump
Model name AUXG18KRLB AUXG22KRLB
Power supply 230 V ~ 50 Hz
Power supply intake Outdoor unit
Available voltage range 198—264 V
Capacity
Cooling
Rated
kW 5.2 6.0
Btu/h 17,700 20,500
Min.—Max.
kW 0.90—5.90 0.90—6.70
Btu/h 3,100—20,100 3,100—22,900
Heating
Rated
kW 6.0 7.0
Btu/h 20,500 23,900
Min.—Max.
kW 0.90—7.50 0.90—8.00
Btu/h 3,100—25,600 3,100—27,300
Input power
Cooling
Rated
kW
1.36 1.71
Max. 2.79 2.90
Heating
Rated 1.58 1.82
Max. 2.79 2.90
Current
Cooling
Rated A
6.0 7.5
Heating 6.9 8.0
Power factor
Cooling
%
98.6 99.1
Heating 99.6 98.9
EER Cooling
kW/kW
3.82 3.51
COP Heating 3.80 3.85
Moisture removal L/h (pints/h) 1.5 (2.6) 2.2 (3.9)
Maximum operating current *1
Cooling
A
12.1 12.6
Heating 12.1 12.6
Fan
Airflow rate
Cooling
HIGH
m
3
/h
1,050
MED 960
LOW 900
QUIET 780
Heating
HIGH 1,050
MED 960
LOW 900
QUIET 780
Type × Q'ty Turbo fan × 1
Motor output W 81
Sound pressure level *2
Cooling
HIGH
dB (A)
33
MED 32
LOW 31
QUIET 28
Heating
HIGH 33
MED 32
LOW 31
QUIET 28
Heat exchanger type
Dimensions (H × W × D)
mm
210 × 2,127 × 13.3
210 × 2,061 × 13.3
Fin pitch 1.2
Rows × Stages 2 × 10
Pipe type Copper tube
Fin type Aluminum
Dimensions
(H × W × D)
Net
mm
246 × 840 × 840
Gross 298 × 960 × 950
Weight
Net
kg
23
Gross 28
Connection pipe
Size
Liquid
mm (in)
Ø 6.35 (Ø 1/4)
Gas Ø 12.70 (Ø 1/2)
Method Flare
Drain hose
Material PVC(VP25)
Size mm Ø 25 (I.D.), Ø 32 (O.D.)
Operation range
Cooling
°C 18 to 32
%RH 80 or less
Heating °C 16 to 30
Cassette grille
(Option)
Material Polystyrene
Color
White
Approximate color of MUNSELL N 9.25/
Dimensions
(H × W × D)
Net
mm
53 × 950 × 950
Gross 110 × 1,000 × 1,010
Weight
Net
kg
6.0
Gross 10.0
Remote control (Option)
Wired remote controller, Wireless remote controller, Mobile app*3 (FGLair
)
NOTES:
Specifications are based on the following conditions:
Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length: 5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
Protective function might work when using it outside the operation range.
*1: Maximum operating current is the total current of the indoor unit and the outdoor unit.
*2: Sound pressure level:
Measured values in manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
*3: Available on Google Play
store or on App Store
®
. Optional WLAN adapter is also required. For details, refer to the setting manual.
- 2 -
1. Specifications
CASSETTE TYPE
AUXG18, 22KRLB
CASSETTE TYPE
AUXG18, 22KRLB

Related product manuals