7-13. Peak cut operation(for 30/36/45 model)
The current value is limited to reduce the power consumption by external input.
Peak cut level Level 1 Level 2 Level 3 Level 4
Peak cut for rated capacity
Forced thermostat
off
50% 75% 100%
NOTES:
During defrost operation, peak cut operation becomes invalid.
Even during the peak cut operation, the operations of current overload, economy, and low noise
are effective and the outdoor unit operates by lowest current of them.
7-13. Peak cut operation(for 30/36/45 model) - (04-37) - 7. Various control