2-16. E: 58. Intake grille error (Indoor unit)
Indicator
Wired remote
controller
Error code E: 58
Detective actuator
Indoor unit main PCB
When the Micro switch is detected open while running
the compressor.
Micro switch
Forecast of cause
Micro switch failure
Shorted connector/wire
Main PCB failure
Check point 1. Check limit switch
Check operation of Micro switch. (any blocking by dust, etc.)
Remove Micro switch and check ON/OFF switching operation by using a meter.
-> If micro switch is detective, replace it.
Check point 2. Check connector (CN11)/wire
Check loose contact of CN11/shorted wire (pinched wire).
-> Replace micro switch if the wire is abnormal
Check point 3. Replace main PCB
If Check Point 1 and 2 do not improve the symptom, change main PCB.
End
2-16. E: 58. Intake grille error (Indoor unit) - (03-20) - 2. Troubleshooting with error code
TROUBLESHOOTING