2. Troubleshooting with error code
2-1. E: 11. Serial communication error (Serial reverse transfer
error) (Outdoor unit)
Indicator
Wired remote
controller
Error code E: 11
Detective actuator Outdoor unit
Main PCB When the indoor unit cannot receive the serial signal
from outdoor unit more than 2 minutes after power on,
or the indoor unit cannot receive the serial signal more
than 15 seconds during normal operation.
Fan motor
Forecast of cause
Connection failure
External cause
Main PCB failure
Outdoor unit fan motor failure
Check point 1. Reset the power and operate
Does error indication show again?
→ If no, go to "Check point 1-2".
Check point 2. Check connection
Check any loose or removed connection line of indoor unit and outdoor unit.
Check connection condition is control unit. (If there is loose connector, open cable or mis-wiring.)
→ If there is an abnormal condition, correct it by referring to the installation manual or the “DESIGN
& TECHNICAL MANUAL”.
Check point 3. Check the voltage of power supply
Check the voltage of power supply
Check if AC 198 V (AC 220 V -10%) to AC 264 V (AC 240 V +10%) appears at
outdoor unit terminal L - N.
+
-
2-1. E: 11. Serial communication error (Serial reverse transfer error) (Outdoor unit) - (03-3) - 2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING

Table of Contents

Other manuals for Fujitsu AUXG22KVLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AUXG22KVLA and is the answer not in the manual?

Fujitsu AUXG22KVLA Specifications

General IconGeneral
BrandFujitsu
ModelAUXG22KVLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals