8-3. Fresh-air control output
Signal linked to the indoor unit fan on can be output.
NOTE: In cold-air prevention control operation, the signal becomes off.
Circuit diagram example
Locally purchased
Indoor unit
control PCB
Connector
1
12 V
on/off
2
Signal
Relay
power
supply
Example: Fan
Connected unit
Example:
Relay unit
*10 m
*: Make the distance from the PCB to the connected unit within 10 m.
Relay spec: Rated DC 12 V, 50 mA or less.
On
Off
Operation
Stop
Indoor unit
Output signal
Optional part
Model name Exterior
UTZ-VXAA
Fresh-air output wire
NOTE: This wire is included in both Fresh air intake kit.
- 23 -