1. Specifications
Type Inverter heat pump
Model name AOHG18LBCB AOHG24LBCB
Power supply 230 V ~ 50 Hz
Available voltage range 198—264 V
Starting current A 7.4 9.9
Fan
Airflow rate
Cooling
m
3
/h
2,380 2,850
Heating 2,080 2,700
Type × Q'ty Propeller × 1
Motor output W 49
Sound pressure level *1
Cooling
dB (A)
50 53
Heating 50 54
Sound power level
Cooling
dB (A)
62 66
Heating 65 66
Heat exchanger type
Dimensions
(H × W × D)
mm
588 × 881 × 18.19
588 × 851 × 18.19
672 × 881 × 18.19
672 × 851 × 18.19
Fin pitch 1.3
Rows × Stages 2 × 28 2 × 32
Pipe type Copper
Fin type
Type (Material) Corrugate (Aluminum)
Surface treatment Corrosion resistance
Compressor
Type × Q'ty Twin rotary × 1
Motor output W 900 1,200
Refrigerant
Type (Global warming potential) R410A
Charge g 1,200 1,500
Refrigerant oil
Type FV50S RB68
Amount
cm
3
400 550
Enclosure
Material Steel sheet
Color
Beige
Approximate color of Munsell 10YR 7.5/1.0
Dimensions
(H × W × D)
Net
mm
632 × 799 × 290 716 × 820 × 315
Gross 692 × 940 × 375 776 × 961 × 450
Weight
Net
kg
36 42
Gross 40 47
Connection pipe
Size
Liquid
mm (in)
Ø 6.35 (Ø 1/4) Ø 6.35 (Ø 1/4)
Gas Ø 12.70 (Ø 1/2) Ø 15.88 (Ø 5/8)
Method Flare
Pre-charge length
m
15 15
Max. length 25 30
Max. height difference 15 20
Operation range
Cooling
°C
-10 to 46
Heating -15 to 24
Drain hose
Material PP+LLDPE
Size mm Ø 13.0 (I. D.), Ø 16.0 to Ø 16.8 (O. D.)
NOTES:
Specifications are based on the following conditions:
Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length: 5 m, Height difference: 0 m.
Protective function might work when using it outside the operation range.
*1: Sound pressure level
Measured values in manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
- 38 -
1. Specifications
OUTDOOR UNIT
AOHG18-24LBCB
OUTDOOR UNIT
AOHG18-24LBCB

Related product manuals